Part number - 824 240 2
Power consumption
- P = 3 W
PROFIBUS protocol options
- PROFIBUS-DP and DP-V1 to IEC 61158
Automatic baud rate detection
- 9.6 kbaud ... 12 Mbaud
Connection technology
- Via 9-pin sub D plug
- Pin assignment to IEC 61158
Bus termination
- Not integrated, implement using suitable PROFIBUS plug with terminating resistors that can be switched on.
Station address 0 ... 125, can be set using DIP switch
Name of the GSD file
- SEW_6003.GSD (PROFIBUS-DP)
- SEWA6003.GSD (PROFIBUS-DP-V1)
DP identity number 6003 hex = 24579 dec
Application-specific parameter-setting data (Set-Prm application data)
- Length: 9 bytes
- Hex parameter settings 00,00,00,06,81,00,00,01,01 = DP diagnostics alarm = OFF
- Hex parameter settings 00,00,00,06,81,00,00,01,00 = DP diagnostics alarm = ON
DP configurations for DDLM_Chk_Cfg
- F0hex = 1 process data word (1 I/O word)
- F1hex = 2 process data words (2 I/O words)
- F2hex = 3 process data words (3 I/O words)
- 0hex, F5hex = 6 process data words (6 I/O words)
- 0hex, F9hex = 10 process data words (10 I/O words)
- F3hex, F0hex = parameter channel + 1 process data word (5 I/O words)
- F3hex, F1hex = parameter channel + 2 process data words (6 I/O words)
- F3hex, F2hex = parameter channel + 3 process data words (7 I/O words)
- F3hex, F5hex = parameter channel + 6 process data words (10 I/O words)
- F3hex, F9hex = parameter channel +10 process data words (14 I/O words)
Diagnostics data
- Max. 8 bytes
- Standard diagnostics: 6 bytes
Tools for startup
- MOVITOOLS ® PC program
- DBG11B keypa