top of page

Part number - 824 240 2
Power consumption

  • P = 3 W

PROFIBUS protocol options

  • PROFIBUS-DP and DP-V1 to IEC 61158

Automatic baud rate detection

  • 9.6 kbaud ... 12 Mbaud

Connection technology

  • Via 9-pin sub D plug
  • Pin assignment to IEC 61158

Bus termination

  • Not integrated, implement using suitable PROFIBUS plug with terminating resistors that can be switched on.

Station address 0 ... 125, can be set using DIP switch
Name of the GSD file

  • SEW_6003.GSD (PROFIBUS-DP)
  • SEWA6003.GSD (PROFIBUS-DP-V1)

DP identity number 6003 hex = 24579 dec
Application-specific parameter-setting data (Set-Prm application data)

  • Length: 9 bytes
  • Hex parameter settings 00,00,00,06,81,00,00,01,01 = DP diagnostics alarm = OFF
  • Hex parameter settings 00,00,00,06,81,00,00,01,00 = DP diagnostics alarm = ON

DP configurations for DDLM_Chk_Cfg

  • F0hex = 1 process data word (1 I/O word)
  • F1hex = 2 process data words (2 I/O words)
  • F2hex = 3 process data words (3 I/O words)
  • 0hex, F5hex = 6 process data words (6 I/O words)
  • 0hex, F9hex = 10 process data words (10 I/O words)
  • F3hex, F0hex = parameter channel + 1 process data word (5 I/O words)
  • F3hex, F1hex = parameter channel + 2 process data words (6 I/O words)
  • F3hex, F2hex = parameter channel + 3 process data words (7 I/O words)
  • F3hex, F5hex = parameter channel + 6 process data words (10 I/O words)
  • F3hex, F9hex = parameter channel +10 process data words (14 I/O words)

Diagnostics data

  • Max. 8 bytes
  • Standard diagnostics: 6 bytes

Tools for startup

  • MOVITOOLS ® PC program
  • DBG11B keypa

Fieldbus interface DFP21B

SKU: C12-4-2
R4 881,99Price
    No Reviews YetShare your thoughts. Be the first to leave a review.

    RELATED PRODUCTS

    bottom of page