TeSys GV motor circuit breaker, 3 poles (3P), 32A/690V, for 3-phase motor applications 15kW@400V. It provides a thermal-magnetic protection with a thermal setting range 24-32A, magnetic tripping at 13xIn, high breaking capacity Icu 50kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

 

Main
RangeTeSys Deca
Product nameTeSys GV2
TeSys Deca
Product or component typeMotor circuit breaker
Device short nameGV2P
Device applicationMotor protection
Trip unit technologyThermal-magnetic

Product dimensions:

  • L:10cm x W:9.3cm x H:4.8cm

GV2P32 - Motor Breaker GV2 3P 24-32A by Schneider Electric

SKU: C10-2-4
R3 482,99 Regular Price
R3 395,92Sale Price
Only 2 left in stock
  • Poles description 3P
    Network type AC
    Utilisation category Category A conforming to IEC 60947-2
    AC-3 conforming to IEC 60947-4-1
    Network frequency 50/60 Hz conforming to IEC 60947-4-1
    Fixing mode 35 mm symmetrical DIN rail: clipped
    Panel: screwed (with 2 x M4 screws)
    Motor power kW 15 kW at 400/415 V AC 50/60 Hz
    18.5 kW at 500 V AC 50/60 Hz
    22 kW at 690 V AC 50/60 Hz
    Breaking capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
    50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
    20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
    4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
    [Ics] rated service short-circuit breaking capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
    50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
    75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
    75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
    100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
    Control type Rotary handle
    [In] rated current 32 A
    Thermal protection adjustment range 24…32 A conforming to IEC 60947-4-1
    Magnetic tripping current 416 A
    [Ith] conventional free air thermal current 32 A conforming to IEC 60947-4-1
    [Ue] rated operational voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
    [Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
    Phase failure sensitivity Yes conforming to IEC 60947-4-1
    Suitability for isolation Yes conforming to IEC 60947-1 § 7-1-6
    Power dissipation per pole 2.5 W
    Mechanical durability 100000 cycles
    Electrical durability 100000 cycles for AC-3 at 415 V In
    Rated duty Continuous conforming to IEC 60947-4-1
    Tightening torque 1.7 N.m - on screw clamp terminal
    Width 45 mm
    Height 89 mm
    Depth 97 mm
    Colour Dark grey