top of page

TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 380V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (45mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Schneider Electric LC1D09Q7 - TeSys D contactor - 3P(3 NO), AC-3, 9A - 380 VAC

SKU: C9-5-3
R1 587,99 Regular Price
R1 548,29Sale Price
  • Motor power kW 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
    4 kW at 380...400 V AC 50/60 Hz (AC-3)
    4 kW at 415...440 V AC 50/60 Hz (AC-3)
    5.5 kW at 500 V AC 50/60 Hz (AC-3)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
    2.2 kW at 400 V AC 50/60 Hz (AC-4)
    2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
    4 kW at 380...400 V AC 50/60 Hz (AC-3e)
    4 kW at 415...440 V AC 50/60 Hz (AC-3e)
    5.5 kW at 500 V AC 50/60 Hz (AC-3e)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
    Motor power hp 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 200/208 V AC 50/60 Hz for 3 phases motors
    2 hp at 230/240 V AC 50/60 Hz for 3 phases motors
    5 hp at 460/480 V AC 50/60 Hz for 3 phases motors
    7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors
    0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
    Compatibility code LC1D
    Pole contact composition 3 NO
    Contact compatibility M2
    Protective cover With
    [Ith] conventional free air thermal current 25 A (at 60 °C) for power circuit
    10 A (at 60 °C) for signalling circuit
    Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
    140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
    Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current 105 A 40 °C - 10 s for power circuit
    210 A 40 °C - 1 s for power circuit
    30 A 40 °C - 10 min for power circuit
    61 A 40 °C - 1 min for power circuit
    100 A - 1 s for signalling circuit
    120 A - 500 ms for signalling circuit
    140 A - 100 ms for signalling circuit
    Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
    25 A gG at <= 690 V coordination type 1 for power circuit
    20 A gG at <= 690 V coordination type 2 for power circuit
    Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
    Power dissipation per pole 1.56 W AC-1
    0.2 W AC-3
    0.2 W AC-3e
    [Ui] rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1
    Power circuit: 600 V CSA certified
    Power circuit: 600 V UL certified
    Signalling circuit: 690 V conforming to IEC 60947-1
    Signalling circuit: 600 V CSA certified
    Signalling circuit: 600 V UL certified
    Overvoltage category III
    Pollution degree 3
    [Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
    Safety reliability level B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
    Mechanical durability 15 Mcycles
    Electrical durability 0.6 Mcycles 25 A AC-1 at Ue <= 440 V
    2 Mcycles 9 A AC-3 at Ue <= 440 V
    2 Mcycles 9 A AC-3e at Ue <= 440 V
    Control circuit type AC at 50/60 Hz
    Coil technology Without built-in suppressor module
    Control circuit voltage limits 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz
    0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz
    0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz
    1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
    Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 20 °C)
    70 VA 50 Hz cos phi 0.75 (at 20 °C)
    Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    7 VA 50 Hz cos phi 0.3 (at 20 °C)
    Heat dissipation 2…3 W at 50/60 Hz
    Operating time 12...22 ms closing
    4...19 ms opening
    Maximum operating rate 3600 cyc/h 60 °C
    Connections - terminals Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
    Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
    Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
    Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
    Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
    Tightening torque Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
    Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
    Auxiliary contact composition 1 NO + 1 NC
    Auxiliary contacts type Type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
    type mirror contact 1 NC conforming to IEC 60947-4-1
    Signalling circuit frequency 25...400 Hz
    Minimum switching voltage 17 V for signalling circuit
    Minimum switching current 5 mA for signalling circuit
    Insulation resistance > 10 MOhm for signalling circuit
    Non-overlap time 1.5 ms on de-energisation between NC and NO contact
    1.5 ms on energisation between NC and NO contact
    Mounting support Plate
    Rail
No Reviews YetShare your thoughts. Be the first to leave a review.