Motor power kW |
3 kW at 220...230 V AC 50/60 Hz
5.5 kW at 380...400 V
5.5 kW at 415 V
5.5 kW at 440 V
7.5 kW at 500 V
7.5 kW at 660...690 V |
Pole contact composition |
3 NO |
[Ith] conventional free air thermal current |
25 A (at 55 °C) |
Irms rated making capacity |
120 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
Rated breaking capacity |
96 A at 440 V for power circuit conforming to IEC 60947 |
[Icw] rated short-time withstand current |
105 A 40 °C - 10 s for power circuit
61 A 40 °C - 60 s for power circuit
30 A 40 °C - 600 s for power circuit |
Associated fuse rating |
10 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit |
Average impedance |
2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Power dissipation per pole |
0.36 W AC-3
1.6 W AC-1 |
[Ui] rated insulation voltage |
690 V conforming to IEC 60947-4-1 |
Overvoltage category |
III |
Pollution degree |
3 |
[Uimp] rated impulse withstand voltage |
6 kV coil not connected to the power circuit conforming to IEC 60947 |
Mechanical durability |
10000000 cycles |
Electrical durability |
1400000 cycles AC-3
300000 cycles AC-1 |
Control circuit type |
AC at 50 Hz |
Control circuit voltage limits |
0.85...1.1 Uc (55 °C):operational 50 Hz
0.3...0.6 Uc (55 °C):drop-out 50 Hz |
Inrush power in VA |
95 VA 50 Hz cos phi 0.75 (at 20 °C)
95 VA 60 Hz cos phi 0.75 (at 20 °C) |
Hold-in power consumption in VA |
8.3 VA 50 Hz cos phi 0.3 (at 20 °C)
8.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
Heat dissipation |
2…3 W for control circuit |
Operating time |
12...22 ms on closing
4...19 ms on opening |
Maximum operating rate |
1800 cyc/h 60 °C |
Connections - terminals |
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end |
Tightening torque |
Power circuit: 1.2 N.m
Control circuit: 1.2 N.m |
auxiliary contact composition |
1 NO |
Minimum switching voltage |
17 V for control circuit |
Minimum switching current |
5 mA for control circuit |
Insulation resistance |
> 10 MOhm for control circuit |
Non-overlap time |
1.5 ms on energisation guaranteed between NC and NO contact
1.5 ms on de-energisation guaranteed between NC and NO contact |
mounting support |
Plate
DIN rail |