CAD overall width |
30 mm |
CAD overall height |
47 mm |
CAD overall depth |
37 mm |
Terminals description ISO n°1 |
(13-14)NO |
Net weight |
0.053 kg |
contacts usage |
Standard contacts |
Positive opening |
Without |
Operating travel |
2.6 mm (NO changing electrical state)
4.3 mm (total travel) |
Operating force |
2.3 N NO changing electrical state |
Operating torque |
0.05 N.m NO changing electrical state |
Mechanical durability |
5000000 cycles |
Tightening torque |
0.8…1.2 N.m conforming to EN 60947-1 |
Shape of screw head |
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver |
contacts material |
Silver alloy (Ag/Ni) |
Short-circuit protection |
10 A cartridge fuse type gG conforming to EN/IEC 60947-5-1 |
[Ith] conventional free air thermal current |
10 A conforming to EN/IEC 60947-5-1 |
[Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to EN 60947-1 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to EN 60947-1 |
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to EN/IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to EN/IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to EN/IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to EN/IEC 60947-5-1 |
Electrical durability |
10000000 cycles, AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
10000000 cycles, AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
10000000 cycles, AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
10000000 cycles, DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
10000000 cycles, DC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
Electrical reliability |
Λ < 10exp(-6) at 5 V, 1 mA in clean environment conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA in clean environment conforming to EN/IEC 60947-5-4 |
device presentation |
Basic sub-assemblies |